Calculator for heating and cooling metering
Mätarkontroll's ICM-T F5 calculator measures both heating and cooling consumption in a single unit. To measure energy consumption, the calculator is combined with a flow meter and a temperature sensor pair.
ICM-T F5 is MID type-approved as a billing meter for heat and complies with the European standard EN 1434. It has two module slots that can be fitted with modules for M-Bus, MODBUS, LON FTT10, analogue output or pulse output. The calculator is powered by 230 V AC or battery. The 8-digit LCD display shows accumulated energy consumption for heating and cooling with corresponding volume, plus instantaneous values for power, flow, flow and return temperature and temperature difference. A configurable memory register gives access to a large number of stored readings.
| Type | Calculator for heating and cooling |
|---|---|
| Flow input | Pulse (reed or OC), 0.1 / 1 / 10 / 100 / 0.25 / 2.5 / 25 / 250 litres/pulse |
| Temperature sensors | Pt500 (Pt100 optional), 2 pockets |
| Display | 8-digit LCD |
| Power supply | 230 V AC or battery |
| Module slots | 2 |
| Type approval | MID (heat), EN 1434 |